book
Dielectric Phenomena in High Voltage Engineering (1915) — part 7 of 12
1 January 1915
where 6 = the voltage to
neutral.
8 = distance between conductor centers. •
r = the radius.
When r and s are in centimeters and e is in kilovolts, g is ex- pressed in kilovolts per centimeter. If eo, which has been called the disruptive critical voUage, is taken for e,
r log, s/r
Qo then is the stress at the conductor surface corresponding to eo, and will be called the disruptive gradient, to distinguish it from the visual gradient gv. Values of go for wires and cables taken under a variety of conditions on the outdoor line are given in Tables LVIII and LIX. These values are corrected to standard tem- perature and pressure by dividing by 6.
- F. W. Peek, Jr., High Voltage Engineering Journal, Franklin Institute, Dec, 1913.
138
DIELECTRIC PHENOMENA
Table LVIII. — Disruptivb Crii^cal Voltage Gradient por Wises (Values Corrected to 76 cm. Barometer and 25 deg. C, Outdoor Line)
Teat No.
Spacing, cm.
Radius, cm.
g. kv./cm. max.
Per cent.
variation
from mean
Per cent.
variation
max. to min.
91
152.0 229.0 410.0 550.0
122.0 183.0 244.0 366.0 488.0
91.4 183.0 275.0 397.0
91.4
183.0
• 214.0
275.0
0.084
31.3 31.6 29.1 36.5
94
92
95
0.164
5.8
134
Avg. =30.9
28.8 27.1 29.0 25.7 25.3
7.9
135
136
137
138
0.259
7.0
125
Avg. =27.2
.28.7 26.5 26.0 26.2
12.7
126
127
128
0.463
6.7
122
Avg. = 26.9
28.7 30.4 30.5 31.0
9.4
123
120
124
4.8
Avg. =30.1
7.6
Total Avg. 29 .
If the values of Co for standard line A (1.8 cm. seven-strand cable) are examined it is found that the average value of go is 25.8 kv. per centimeter maximum. For cables between 0.583 cm. and 1.18 cm. in diameter and various spacings, the average value of go is 25.6 kv. per centimeter maximum, or, in other words, go is constant for commercial sizes of cables, at practical spacings, and is 25.6 kv. per centimeter maximum. In determining the value go for seven-strand cables r was taken for convenience as the outside radius. Hence the above go is not the actual go as ob- tained for wires, but is an apparent go. The actual go may be
CORONA LOSS
139
obtained by taking some mean radius ft between the outside radius r and the radius to the point of contact of the outside strands ri. rt approaches r in value as the number of strands is increased.
Table LIX. — Disruptive Critical Voltage Gradient por Cables (Values Corrected to 76 cm. Bar. and 25 deg. C, Outdoor Line)
Test No.
Spacing, cm.
RadiiiB, ezn.
g. kv./cm. max.
Per cent.
variation
from mean
Per cent.
variation
max. to min.
73
91.4 152.0 244.0 310.0 432.0
91.4
91.4
183.0
275.0
366.0
310.0 310.0 310.0 310.0 310.0 310.0 310.0 310.0 310.0 310.0 310.0
0.292
26.5 24.0 23.9 23.9 25.0
80
1
79
77
82
0.476
7,3
100
Avg. =24.7
25.5 26.2 26.0 26.4 28.1
9.8
115
116
,
117
•
118
Line A 0.590
6.4
18
Avg. = 26.4 — 1. 2. 3. 4 25.5 26.0 25.3 25.8 26.5 26.1 25.7 26.0 25.8 25.1 26.0
9.3
36
•
37
84
t
101
103
104
105
109
119
119
Total
2.7 5.5
Avg. =25.8 Avg. =25.7
5.3
8.1
The values of Qo for wires varying in diameter from 0.168 cm. to 0.928 cm. and for spacings from 90 to 600 cm. are constant within the limits of experimental error. This more than covers the commercial range. The mean max. value is:
00 = 29 kv. per cm. at 25 deg. C, and 76 cm. barometric pressure.
140
DIELECTRIC PHENOMENA
Considerable variation should be expected in Qo values obtained on a long outdoor line, due to
-
Necessarily imperfect conductors, kinks, etc., in an outdoor line of this length.
-
Progressive change in the value of successive points on a given curve due to slight changes of wave shape, etc., as the vol- tages are increased, and the apparent shift of Co,
The close agreement of Qo for wires is for the above reasons remarkable.
Discrepancies due to progressive change are not to be expected for standard line A to any great extent as the conductor spacing was always the same, and test conditions were kept as nearly constant as possible.
M
8
ou 40 90
V
Om
2:8.8
Av»
X
X
ft
\vir
ao
10
9*
«.»
o ■
^-1
'
,
1
I
( 1
i
4
.
S
1
s
f
7
Badlua la em9
FlG. 128.— . 90 for wires and cables. (Data from Tables LVIII and LIX.)
The above data shows that go may be considered constant for diameters of conductors and spacings within the practical range. This immediately suggests that Qo is the actual rupturing gra- dient of air or identical with Qo of the expression for visual corona. This was further investigated over a greater range on the indoor line.
Qo cables
- — ,- - = rrio
Qo wires
where mo is a fraction which approaches unity as the irregularity of the surface is reduced, or number of strands increased. Then
Co = dm„gor log* s/r (35)
(See curve. Fig. 128.) The loss equation may now be written
P =
241
(/ + 25)\A7s(e - Coy 10-'^ kw./km. (34)
CORONA LOSS
141
where p expresses the loss above the visual critical voltage e«, and Co is given in (35).
Investigations on the indoor line over a range covering small conductors show that the disruptive gradient may be considered for all practical purposes, constant when the conductor radius is greater than 0.20 cm. As the size of the conductor is decreased the disruptive gradient increases very rapidly. If the disruptive gradient for any size of conductor is called Qd we have found that this law may be expressed:
Qd
= Mr
0.30
^/^r
1
(1 + 230 r
^)
Bd = Qd r log. -
r
(36) (35a)
160 140 180 120 110 BlOO S.90
2 70 9^60
**«) 40 80 80
,
t
%
is
r'^sfe:
S^^^~~~—
Oo^^^ _.-
.1
.2 .3 .4 .6 .6 .7 .8 .9 LO
Badlui in cm.
Fig. 129. — Ck)mparison of g^, gdi and Qo. {Qd values from Table LX-)
Thus, when r is large (above 0.2 cm.) practically Qd = Qo, and where r = o, (7d == gv.
This apparent increase in disruptive gradient for small con- ductors gives the impression that the residual from the very highly ionized air resulting at each cycle in effect increases the size of the conductor. Thus, the Qd formula is the same as the g« formula with the energy distance term apparently modified or lessened by the residual ionization at each cycle. Qo results for large conduct- ors. Measured values of Qd for different conductors on the indoor line are given in Table LX. Calculated and measured values are plotted in Fig. 129.
The corona loss equation over a greater range of conductor diameter and spacing may thus be written
142
DIELECTRIC PHENOMENA
-
-
- 0.04 p = 241(/ + 26)/ (c - a) 10-»kw./km. (34a)
-
where e<j is obtained from equation (35a).
Tablb LX
Test No.
r cm.
Od maximum measured
Qd maximum calculated
12 B
0.032
67.5
70.7
13 B
0.032
70.3
70.7
14 B
0.032
71.0
70.7
18 B
0.032
71.0
70.7
15 B
0.032
71.0
70.7
16 B
0.032
71.0
70.7
19 B
0.032
69.6
70.7
17 B
0.032
71.2
70.7
20B
0.032
69.5
70.7
21 B
0.032
69.3
70.7
Avg.-70.0
27 B
0.057
51.7
•51.3
26 B
0.057
51.3
51.3
25B
0.057
51.7
51.3
24 B
0.057
51.3
51.3
Avg. =51 .6
«
SOB
0.071
45.4
45.4
33 B
0.0914
39.4
39.4
32 B
0.0914
39.4
39.4
42 B
0.105
42.2
37.6
41 B
0.105
42.2
37.6
37 B
0.105
42.5
37.6
Avg. =42.3
45 B
0.164
36.5
33.0
44B
0.164
33.6
33.0
Avg. =35.1
49 B
0.256
30.8
31.1
48 B
0.256
32.1
31.1
47 B
0.256
33.2
31.1
Avg. =32.0
56 B
0.464
31.8
30.2
55B
0.464
31.8
30.2
54B
0.464
31.5
30.2
Avg. =31.7
CORONA LOSS
143
It may be interesting to note that equation (34) may be written in terms of the gradient, thus
p = A'VTTs (/ + 25) (log ^) * Cr») (g - Qo)^ X lO"'
Fig. 130 shows measured curves plotted between g and p for a given wire at three different spacings. These curves all intersect the axis at go max. = 30, at 5 = 1.0.
10 2080406060708090 100 110 120 ISO 140 160 160 170180
Appftrent Sarfaca Oradiauk
Fig. 130. — Relation between power loss and apparent surface gradient.
Losses Near the Disruptive Critical Voltage — Co- — If the con- ductors could be made perfect no appreciable loss would occur below the visual critical voltage. However, near the starting point of corona two effects occur, which cause a deviation of the loss from the quadratic law, equation (34), and which affect the loss in opposite directions:
(a) With perfect conductors loss of power does not begin at the voltage Co, at which the disruptive gradient is reached at the conductor surface, but only after the disruptive strength of air has been exceeded over a finite and appreciable distance a from the conductor; that is, at a higher voltage e». Since the con- vergency of the lines of dielectric force is great at the surface of small conductors, with such conductors, a considerable increase of the voltage is required to extend the disruptive gradient to some distance from the conductor, and Cv is considerably higher than Co. With such conductors there would be no loss until e, were reached. The loss would then suddenly take nearly the definite value calculated for this applied voltage from equation (34). Even with polished conductors, in practice the decrease of loss below that given by equation 34 is appreciable with small conductors within the range between e© and Cv, as seen in Fig. 131.
144
DIELECTRIC PHENOMENA
2.2
2.0
1.8 1.6
1.4 0,1.2
I
§1.0
- .8 .6
.4
.2
/
r
/
/
I
7
/
1
';
1
1
7
Lsarec
Losi
J
u
1
Quad .00221
ratic
/
1
t.
y.
4
f
60 20
60
80
100 120
Between Linei
80 40 60 60
KUovolU Effective ^^ Neutral
With large conductors, however, the less convergency of the
lines of dielectric force at the conductor surface requires a less voltage increase beyond Bo to extend the disruptive gradient to some distance from the conductor; eo and e, are therefore closer together, and this decrease of the loss below the theoretical value given by equation (34) is not appreciable.
(6) As the conductor sur- face can never be perfect, some loss of power occurs at and below the disruptive criti- cal voltage at isolated points of the conductor, where irreg- ularities of the surface,
Fig 131.-Ck>rona loss for small con- scratches, spots of mud or ductors near the cntical voltage. . *• i_
No. 8 copper. Diameter, . 328 cm. dirt, etc., give a higher poten-
Length, 29,060 cm. Spacing, 122 cm. tial gradient than that corre-
Temp. 1.5. Bar., 76.6. Line B. spending to the curvature of
the conductor surface. With small conductors, this loss is rarely appreciable, since the curvature of the con- ductor surface is of the same magnitude as that of its irregu- larities. It becomes appreciable, however, for larger conductors, as seen in Fig. 132. This excess of the loss beyond that given by the quadratic law equation essentially depends on the con- ductor surface and is ^^^' ^^2* — Corona loss for large conductors near ^, , ,, ' , the critical voltage. (Data same as Fig. 115.)
the larger the rougher
or dirtier the surface is. It is a maximum at the disruptive critical
1.6
L4
1.2
1.0
I
o
.8
.6
.4
.2
/
/
1
V,'
^
uare(
ILosi
i
//
'Qum
Iratic p -.
»116
-0
*. / d
^Bxc<
'o)«
__J— <
*-^
'J^
f ^.
100 60
110
120 60
130 140 160 160 170 180 190 200
Between Llnei 70 80 90 100
KilovoltB Effeotive To Neutml
CORONA LOSS
145
voltage Cof and decreases above and below 6«, and is with fair accuracy represented by the probability curve:
p = ge
(37)
where 9 is a coefficient depending on the number of spots, and h is a coefficient depending upon the size of spots.
Snow, sleet and rain losses seem to be of the same nature, but frequently of far greater magnitude.
Equation (37) is probably of no practical importance as the loss is small, and q and h naturally cover a wide range of values, depending upon the condition of the conductor surface. Experi- mental values near Co are taken from Table XLIV and tabulated in Table LXI, together with, values calculated by the quadratic law. Corresponding experimental and calculated values are subtracted and also tabulated.
Table LXI.— Line A 1-2-3-4 from Table XLIV, Test 36
c« = 0.0115 Co = 72.1
KOovolts between conductors e'
Kw. exp. Po
Kw. p - 0.01 15(e - ea)'
1
Excess loss Pi - (Po - P)
log. Pi
1
(«• - e)»
120.4
0.11 0.15 0.22 0.40 0.79 1.42
0.11
0.15 0.22 0.30 0.16 0.08
2.40 2.71 3.09 3.40 2.77 2.10
146.5
130.2
49.0
139.2
6.2
150.0 150.0 165.8
0.10 0.63 1.34
8.5 54.7 11.7
Fig. 132 is plotted to a large scale to show the excess loss near 60. As this is for large conductors, Co and e^ are near together, and the effect of (Jb) predominates. In order to see if equation (37) holds, write
log. pi = log g - ft(6o- e)*
Then the curve between log pi and (Co — ey should be a straight line. This is shown in Fig. 133. Values of q and h are of the following order for Line A :
Test No.
q per cm. total conductor
h
30 105 103
3 . 19 X 10-« 2.47 X 10-« 2.74 X 10-«
-0.0220 -0.0208 -0.0304
146
DIELECTRIC PHENOMENA
Fig. 131 is plotted from values for a small smooth conductor. Here Co and 6« are far apart, and as the curvature of the conductor surface is of the same magnitude as its irregularities they do not
greatly influence the loss. The (a) effect here predomi- nates — that is, the loss near 6c is lower than that shown by the quadratic law.^
The loss between eo and 6« is unstable as it depends upon surface conditions. In aU cases the quadratic law is closely followed above c„, and on large practical sizes of con-
M
O l4 .
^
^
*^
^
«
2
5
6
7
6
1
W
125
160
Fio. 133. — Determination of equa- tion (37).
ductors with sufficient accuracy over the whole range.
Temperature and Barometric Pressure. — Values of the dis- ruptive critical voltage e© covering a considerable temperature range are tabulated in Table LXIL Correction is made to a
Table LXII. — Temperatube and Disruptive Critical Voltage e«
(Standard Line A 1-2-3-4)
Test
Temperature
Bar. cm.
e'o ky. bet. lines
e'o corr. to 76 cm.
1/e'o
Weather
No.
Wot
Dry
18
16.0
18.5
75.5
138.5
140.0
0.00715
Bright sun
15
20.0
22.0
75.2
140.0
142.0
0.00705
Cloudy sun
37
10.0
13.0
75.7
141.0
142.0
0.00705
Bright sun
36
10.0
12.0
75.0
144.2
146.5
0.00683
Cloudy
100
-3.0
-2.0
73.9
148.8
150.8
0.00663
Hazy sun
84
1.0
3.0
75.2
149.0
151.0
0.00662
Cloudy
101
-1.0
-1.0
74.7
153.8
156.8
0.00638
Cloudy
103
-4.9
-4.5
75.7
155.3
156.7
0.00638
Sun
104
-9.5
-9.5
76.2
157.0
157.0
0.00637
Sun
119
-6.5
-6.0
76.5
156.6
156.1
0.00642
Sun
105
-13.0
;-13.0
1
76.2
161.0
161.0
0.00622
: Sun
1
barometric pressure of 76 cm. on the assumption that e'o varies directly with the pressure. In Fig. 134 l/e'o is plotted with temperature. The straight line through these points cuts the temperature axis at —273 deg. C. or absolute zero. Temperature was always measured in the shade. The points that do not fall
^ This condition is likely to obtain to a greater extent at high altitudes as Co and e« are farther apart.
CORONA LOSS
147
well on the curve are the Bummer sunny day points. This is what would be expected, as the conductors were at a higher tem- perature than the temperature read.
Fig. 134 shows that the disruptive critical voltage or the dis- ruptive gradient varies inversely as the air density; The data range, however, is not great.
The density of air at 25 deg. C. and 76 cm. barometrie pressure is taken as the standard.
Humidity, Smoke, Wind. - Humidity. — ^Line A was kept ® as a standard throughout the "'' tests. A careful study of the disruptive critical volt^^ and
c* shows no appreciable e£Eect '
of either humidity or "vapor products."' (See Table LXIII.) Visual tests, made on two short parallel wires indoors over a great humidity range, also bear this out.
Table LXIII.— Stand a hd Line A.' Condijctor8 1-2-3-4
TMtta.
T™p.»tur,
bamidity
V.por
g, mduoed to
25 do.. C.. 78
om, bar.
Wet
Dry
15
20.0
22.0
0.84
0.56
18.8
IS
16.0
18.5
0.75
0.35
18,6
36
10.0
12.0
0.78
0.25
18,8
37
10.0
13.0
0.67
0.21
18.3
84
1.0
3.0
0.69
0.11
18.7
101
-1.0
-1,0
1.00
0-17
19.2
103
-4,9
-4.9
1,00
0,13
18.0
104
-9.6
-9.5
1,00
0.08
18.6
105
-13.0
-13.0
1,00
0.06
18,8
109
-2.0
-2,0
1.00
0,12
18.7
Theoretically there should be an appreciable effect of humidity
' Merahon, High Voltage Measurementa at Niagara, A.I.E.E., June 30, 1908.
- Line A was kept at constaot test conditions for use as a standard in the Btudy of varying atmospheric coDditioos, etc.
148 DIELECTRIC PHENOMENA
on Co, since even if the water vapor, which may be considered as a gas dissolved in air, has a different disruptive gradient than air, the percentage of the gas in the mixture should be too small to cause any appreciable change. It has been suggested that "vapor products" is a measure of ionization and, in that way, the critical voltage varies with vapor products. This does not seem likely, because with all ordinary atmospheric air the per- centage of ionization is so small that it would not be expected to produce any effect. To test this, the visual critical point was determined on two parallel wires. The room was then closed and the wires were run at a point very much above this critical point for about an hour, or until a very intense odor of ozone filled the room. The voltage was then removed and the surface of the wires cleaned in order to remove oxidization. The critical point was then redetermined and found to be the same, although the amount of ionized air was many times that which could be expected in free atmospheric air. Of course if the percentage of ionization were great enough, as for instance in an ozone machine, a change in the disruptive strength would then be expected.
It has been claimed that ultraviolet light reduces the sparking point. This is not borne out in tests, where any quantity of continuously applied power is involved. Though ultraviolet light, ionized air, and various radiations cause the small energy in condensers to discharge when applied over comparatively great time; in case of large energy discharge in a very short time, as spark discharge, and corona due to continuously applied voltages, no appreciable effect should be expected, or can be observed, since the discharge which takes place by ionized air is not of the same order of magnitude as that produced by the spark discharge. The time required for a given voltage to pro- duce ionic saturation or discharge, should, however, be less with high initial ionization than with low initial ionization. Hence for impulse voltages of steep wave front and short duration, the spark voltage may be affected by initial ionization. This is further discussed in Chapters IV and VIII (page 198).
It is quite probable that humidity has some slight effect on the loss after corona has once formed due to the change of the gas into vapor and the agglomeration of the water particles by the ions. This is noticed in the spark-over between needle points at very high voltage. In this case there is a very heavy brush discharge before spark-over. The sparking voltage increases
CORONA LOSS 149
with increasing humidity, due to the fog formed, when there is not a mixture of two gases, air and water vapor, as in the case where humidity is concerned, but actual water particles are in the air. Steinmetz has observed that fog actually raises the striking distance between needle points. The effect of humidity on the spark discharge observed by the author is discussed in Chapter IV. Greater loss should be expected in corona measurements during fog due to charge and discharge of the water particles. This causes loss at lower voltages and has the effect of decreasing the critical point.
While humidity has no effect on the starting point of corona, an effect might be expected on the loss after the discharge had already started. The reason that this is inappreciable is because the corona discharge from wires covers very little space.
Smoke, — It was difficult to get measurements to show the effect of smoke, as the prevailing winds were over the fields toward the city. At one time, however, during a change in the wind thick smoke was blown over the line from smoke stacks of a fac- tory, and the loss was increased. This, however, will probably not be a serious consideration in practice.
Wind. — ^Losses measured during very heavy winds show no variation from losses measured during calm weather. That the losses do increase with increasing air velocity has been shown in laboratory apparatus. There is, however, no appreciable effect due to the comparatively low air velocity in practice.
Moisture, Frost, Fog, Sleet, Rain and Snow. — During some of the first tests it was noted that the losses were sometimes greater on the "going-up curve" than on the "coming-down curve," especially in the early mornings after heavy dew. The losses became less after the line had been operated for a while at high' voltage. Fig. 135 shows this well for a conductor with a coating of frost. This excess loss was thought at first to be due to leakage through moisture on the insulators. Insulators were put up without line wires, but measurements showed a very small insulation loss even during storms. It was then concluded to be due to moisture on the conductors themselves. Visual tests made on short lengths of wet and dry cables showed this in a very striking manner. Two parallel dry cables were brought up to the critical point. Water was then thrown on the cables. What had been a glow on the surface of the dry cables now became, at the wet spots, a discharge extending as much as 5 to 8 cm.
10
150 , DIELECTRIC PHENOMENA
from the cable surface. This discharge reminded one of an il- luminated atomizer. Illustrations, Figs. 67 and 6S show this, but a greater part of the effect is lost in reproduction. The wires became quite dry and down to normal discharge after runnii^ at high volt^e for a I very few minutes. Biiov-iu ».eti.. ,j,jjg curves, Fig. 136,
Fig. 135. — Corona loss with frosty and dry . , j„_:„„ j.i,„ j„„
conductors. taken during the fog
(Conductor length, 109,500 cm. Spacing, also show the combined 310 cm Diameter. 1.18cm. 3/0,7;*trand effect of condensed cable. Line A. Temp.,-2°C, B»r..74cm.)
moisture on the cables,
and free water particles in the ear. The moisture particles on
/
/
/
1^
^
/
s
I.
1>
r
^
_1
f.-y
_
_
_
_
w
i; - - J
u L
i I-
u ^i
I ? U i ^
1 TT-Pf
, ' • 9
J 2 *'
; , -i>
I ' w
! z li
/ .1
\ ^ -J/-
'ssagag 31 sssia
(Conductor length, 109,500 ci Diameter, 1.18 cm. Spacing, 310ci
the conductor become charges and are repelled. The particles
CORONA LOSS
151
in the air also become charged and discharged thus increasing the loss very greatly above that for dry conductors.
The losses during snow and rain storms are much greater than fair weather losses at the same temperature and barometric
r
^tu.
--- -#/
100 110 120 uo uo uo uo m i£D 1)0 a» 110 m no
Fi<3. 138. — Corona Jobs during sleet storm.
(Conductor length, 100,500 cm. Diameter, I.IS cm. Spacing, 310 cm.
3/0,7-fltrand cable. Line A. Temp., - 1 .0. Bar., 75.4.)
pressure. In Fig. 137 the actual measured loss is plotted, and also a corresponding calculated fair weather loss. The difference between the two curves shows the excess loss due to snow. The effect of snow is greater than that of any other storm condition. This is because the particles are larger and a greater num- ^ bar strike the line, or come lo near the line. ^
The sleet curves are of s^ special interest. Sleet had ^o already started to form on the a ' conductors, and was still falling , when the tests were started. s Fig. 138 shows the loss curves. * After the curves were taken the line was kept at 200,000 volts for over an hour with no apparent diminution of sleet. This seems to show that sleet
will form on high-voltage trans- Temp. 10.0. Bar, 76.) misaion lines.
The day after these tests were made was bright and clear and the conductors were still coated with sleet. A set of readings was taken, and it is interesting to note that the excess loss here is as great as when sleet was falling. (See Fig. 139.)
(Conductor length, 106,500 cm. Diameter, 1.18 cm. Spacing, 310 3/0,7-strand cable. Line A.
152
DIELECTRIC PHENOMENA
The excess loss for sleet, rain or snow storms (over the fair weather loss) seems with increasing voltage to approach a maxi- mum and then to decrease again (the latter at a value very far above the disruptive critical voltage), and the curves of loss seem to have the general shape of the probability curve, as is to be expected theoretically.
The above readings show the im- portance of taking weather conditions into account in the design of high- voltage transmission lines.
Very High Frequency. — Corona losses at very high frequency are diffi- cult to measure. The curve in Fig. 140 is interesting. The drawn curve is calculated from formula 34(a); the points are measured values. Power was supplied from an Alexanderson 100,000-cycle alternator. The power ^'''' SlSueSc^^^^^ ** WM measured by adjusting reactance (Two parallel wires, and capacity until unity power factor Spacing, 67 cm. Radius^ ^g-g obtained. The watts input was wire, 0.127 cm. / = 100,000 ^, ^, j x r ix j
~. Total length, 200 cm.) then the product of volts and amperes Tests by Alexanderson. g^g measured by hot wire meters.
This good check seems to show that the formula applies over a large range, but complete conclusions cannot be drawn from this small amount of data.
600
1
/
Ourre OftlcaUted — , Points Heaaored X 1
f
400
/
,800
1
' 1
1
/
aoo
(■
j
100 60
/
y
f
%
/
14 16 1820a24M2880
Kilo-Volts SffectiTe,S«tw«eo Linos
CHAPTER VI
CORONA Aim SPARK-OVER IN OIL AND LIQUID INSULATIONS
The most common liquid insulation is transformer oil obtained by fractional distillation of petroleum. This oil has various characteristics, as flashing point, freezing point, viscosity, etc., depending upon the specific use to which it is to be put. The average characteristics of transformer oil are as follows:^
Medium
Light
Flashing temperature
Burning temperature
Freesing point
Specific gravity at 13.5 deg. C
ViscoBity at40deg.C. (Saybolt test) Acid, alkali, sulphur, moisture
180*'-190° C. 206''-216«' C. -10** — IS*' 0.865-0.870 100-1 10 sec. None
130^-140*' C. 140'»-150'» C. -15* — 20* 0.845-0.850 40-50 sec. None
Various other oils are insulators, as gasoline and cylinder oil; animal oils, as fish oil; vegetable oils, as linseed oil, nut oil, china wood oil, etc. AH of these when pure have the same order of dielectric strength.
The so-called compounds made by dissolving solid gums in oil to increase viscosity are generally unreliable, unless used dry as varnish. Under the dielectric field the dielectrics of different permittivities tend to separate, and there is considerable loss. As in air there is very little loss in pure oil until local rupture, that is, brush discharge or corona, occurs.
The dielectric strengths of oils are usually compared by noting the spark-over voltage between two parallel brass discs 1.25 cm. in diameter, and 0.5 cm. separation. The spark-over voltage for good oils in the above gap should be between 50 and 70 kv. maximum, and hence, if the voltage wave is a sine, from 35 to 50 kv. eflfective.*
» Tobey, Dielectric Strength of Oil, A.I.E.E., June, 1910.
- The breakdown voltage of oil like that of air depends upon the maximum point of the wave.
153
154
DIELECTRIC PHENOMENA
Different Electrodes. — In Fig. 141 are plotted spark-over curves for^ifferent electrodes in good transformer oil. The character- istics are very much the same as for air excepting the apparent strength is very much higher.
Effect of Moisture. — The slightest trace of moisture in oil greatly reduces its dielectric strength. The effect of moisture is shown in Fig. 142(a) for the standard disc gap. Water is held in suspension in oil in minute drops. When voltage is applied
aoo
280 260 240 220 200
/
/»
em.
8pbe
ret ( »».)
•
/
/
/
<,
10 I Co
:m. I i«c« . Dlftf on 1
d(ei
/
y
/
1
A
/
/
y
/-
•y
cm.
8ph<
rea
y
/
3
CiflO
/
/
^
/^
,/^
:<•
BdlM
Sl40 e
Bl20
)
'
/
A
/
y
r —
y
/
I
f
J
/
100 80 60 40 20
f
/
/
A
/
'/
/
(Tei
ip.8
'o)
•
1284 6678910 SpAciog cm.
Fia. 141. — Spark-over of various shaped electrodes in oil.
these drops are attracted by the dielectric field. Thus they are attracted to the denser portions of the field and may form larger drops by collision. When attracted to, and after touching a metal part, and thus having the same potential, they are imme- diately repelled. If the field is uniform the drops form in conduct- ing chains along the lines of force. It can be seen that the effect of moisture should vary greatly with the shape of the electrode, and with some shapes the moisture may even be removed from the space between the electrodes by the action of the field, in which case its presence would not be detected by low-voltage
CORONA AND SPARK-OVER IN INSULATIONS
155
breakdowns. In transformers moisture will generally be attracted to points under greatest stresa. The most effective way of removing moisture is by filtration through blotting paper. Dirt in oil may have an effect very similar to moisture and the small conducting particles be made to bridge between electrodes by the dielectric field.
Temperature. — Temperature over the operating range has very little bifluence on the strength of oil. The strength increases at the freezing point. The curve is shown in F^. 142(6). The insulation resistance is also shown. The increase in strength
(o)
(b)
"V
"-
'
with temperature is only apparent and due partly to the decreas- ing insulation resistance which allows more current to flow through the oil, which tends to even up the stress, but mostly to the drying out of moisture particles by the high temperature. The increase at freezing should be expected, as an actual improve- ment in dielectric properties results. For a perfectly dry oil the strength actually decreases with increasing temperature or den- sity, as in the case of air. The specific resistance of transil oil ia approximately: Temp., C Ohms, cm. cube.
100
250 X 10" 100 X 10'» 15 X 10"
The permittivity is approximately 2.6 times its specific gravity and thus decreases with increasing temperature.
Spark-over and Corona in Oil. — A phenomenon similar to corona in gases also takes place in liquid insulations, as oil, due to a tearing apart of the molecules. Corona in oil is not as steady or definite as in air. It appears to start quite suddenly and extend
156
DIELECTRIC PHENOMENA
much farther out from the electrode than corona in air. It is much more difficult to detiBct the starting point, and unless the conductors are very small or far apart (s/r large) corona does not appear before spark-over. For instance, in the Table LXVII when the outer cylinder is 3.81 cm. radius and the inner 0.0127cm. radius (R/r = 300), the corona and spark-over voltages are prac- tically the same (see condition for spark-over and corona, Chapter II). The absence of corona, or rather the simultaneous appear- ance of corona and spark-over, unless the wires are very small or far apart, seems to mean that the mechanism of breakdown in oil is very similar to that in air but the energy distance in oil is much greater. Thus, as the voltage is increased, corona rupture occurs out to the energy distance; this increases r to the condition for spark-over.
R = ^<t
(r + energy distance broken down) Vi
and spark follows. Therefore, the spark-over voltages and
Table LXIV. — Dielectric Strength op No. 6 Transil Oil — Spark-over
BETWEEN Spheres
Radius of spheres, em.
Needles
Spacing, cm.
• 0.169
0.555
1.27
3.12
6.25
Kv. max.
Gra- dient max. kv./cm.
Kv. max.
Gra- dient max. kv./cm.
Kv.
max.
Gra- dient max. kv./cm.
Kv. max.
Gra- dient max. kv./cm.
Kv. max.
Gra- dient max. kv./cm.
Kv.
max.
0.129 198
44.6 50.5 59.2 65.0
71.1 81.0
449 360 365 360
364 368
48.0
394
47.1
364
1 1
0.264 322
73.9
333
73.5
310
74.3
288
74.8
289
0.378 508
90.0
295
•
99.0
222
105.0 220
107.0" 214
650
41.6
0.766
1.010 1.270 1.780 2.540
3.810 5.080 7 620
89.9
97.6 104.0 111.0 124.0
145.0 168.0
353
358 361 384 416
470 542
106.0
112.0 116.0 131.0 149.0
172.0 191.0
225
192 176 171 174
184 192
117.0
187
128.0
146.0 171.0 203.0 240.0
266.0
182
166 158 137 122
103
132.0
159.0 177.0 214.0 245.0
- 0|
180
166 147 130 110 '
90
157.0 165.0 185.0
206.0 231.0
158 143 130
131 133
67.0
84.0
108.0 124.0
166.0
10 150
203.0
Oil between standard discs 0.5 cm. apart tested 68.5 kv. max. 25 deg. C.
CORONA AND SPARK-OVER IN INSULATIONS
157
Table LXV. — Spark-over between Parallel Plates in No. 6 Tranbil
Oil
ekv. max.
X
spacing cm.
kv./cm. (max.)
Remarks
34.6
0.254 0.508 0.762
1.015 1.270 1.525
1.270 1.525 1.778
2.03 2.29
2.54 2.79
3.05 3.30
3.56 3.81
1.27 2.54
5.08 7.62
136.3
102.8
93.0
m
104.8 89.6 82.8
98.2 90.0 85.0
82.2 81.8
77.2 76.6
69.5 73.2
72.2 63.0
88.8 61.0
41.7 35.0
52.3
71.0
106.0 114.0 126.5
•
hn=.rfT'
^
l^'lliV
125.2
Distance 0.476 en
between 1.
small and large
discs "
137.5
158.0
167.7
187.3
196.5
Same as above, except distance small and large discs = 1.58 cm.
between
214.5
212.7
242.0
257.5
241.0
113.2 155.5
212.0 269.0
4-in. flat discs, 0.5-cm. radius edge.
Table LXVI. — Corona in Oil, Wire and Plate (Distance of wire from plate = 16.5 cm.)
Ky. efif.
Radius wire, cm.
0» kv./cm. eff.
0*
kv./cm. max.
50
0.025
278
393
60
0.050
185
262
80
0.0635
201
284
100
0.1520
122
173
55
0.00508
615
870
158
DIELECTRIC PHENOMENA
corona voltages up to fairly high ratios of R/r are the same, and may be used in determining the strength of oil.
Table LXVII.— Spabk-ovbb Voltages for No. 6 Tranbil Oil Con- centric Cylinders
R om.
r cm. 1
Kv. eff.
Kv. max.
Oa max. kv./cm.
1
R
r
RemarlcB
3.81
0.032
45.3
64.0
420.0
5.61
120\00
Tests made in
3.81
0.238
60.0
84.8
127.7
2.05
16.00
long cylinders
3.81
0.317
60.5
85.5
108.1
1.77
12.00
with belled
3.81
0.635
69.5
98.3
86.3
1.26
6.00
ends. Oil be-
3.81 3.81 3.81 3.81
0.794 0.952 1.111 1.270
75.0 73.0 76.7 76.0
106.1 103.2 108.5 107.5
85.5 78.1 79.4 77.0
1.12 1.02 0.95 0.89
4.80 4.00
3.00
tween standard discs 0.5 cm. apart tested 58 kv. (max.) 25 deg. C.
3.81
1.587
73.7
104.3
75.1
0.79
2.40
3.81
1.905
66.3
93.7
70.7
0.72
2.05
3.81
2.540
45.5
64.3
62.4
0.63
1.57
6.67
5.560
29.2
41.3
40.6
Tests made on
6.67
5.080
43.7
61.8
44.8
short cylinders
6.67
3.970
70.1
99.2
48.1
where field is
6.67
3.240
84.4
119.5
51.0
somewhat dis-
6.67
2.230
105.8
149.7
61.2
torted.
6.67
1.955
105.0
148.5
61.9
6.67
1.615
103.5
146.5
64.0
6.67
1.270
101.3
143.2
67.5
6.67
0.953
98.3
139.0
75.0
6.67
0.635
94.0
133.0
89.2
6.67
0.477
91.5
129.5
102.8
6.67
0.318
85.3
120.7
121.0
6.67
0.159
65.2
92.2
155.5
6.67
0.079
62.2
88.0
251.4
11.42
3.930
144.0
203.5
48.3
11.42
2.280
163.0
230.4
63.0
11.42
1.910
158.0
223.2
64.5
11.42
1.270
160.0
226.0
81.5
11.42
0.880
148.0
209.0
93.0
11.42
0.520
90.0
127.3
79.5
The strength of oil for different sizes of wire from Table LXVII is plotted in Fig. 143. The curve is similar to that for corona in air. Fig. 144 shows that a straight line relation holds approxi-
CORONA AND SPARK-OVER IN INSULATIONS
159
mately between —7= and g^. Values are not used when R/r > 3.5. Thus, as in the case of air:^
g'v = g'ol
1 +
Vr)
max.
g^ = 36(1 + --^jkv./cm.
Qv = 25.5( 1 + —V I kv./cm. effective si
sine wave.
200 180 160 IM
00
40
ao
?— —
. — i^HBM .«^aa ^M^M- ^^.^^ ^
.4 .8 U U 2.0 2.4 2.8 8.2
Badltti-em.
FiQ. 143.— Strength of oil. (Concentric cylinders — gv at surface of inner cylinder.)
aoo
180
.160
8
-^40 Sl20
100
80 60
40
20
— ^
8
L2
1.6 ^ 2.0
2.4 2.8 8.2 8.6
Fia. 144. — Strength of oil. (Method of reducing values given in Fig. 143 to equation.)
The energy distance is 1.2/r or almost four times that of air, indicating that a greater amount of energy is required to rupture oil, or a greater number of collisions are necessary before ionic
^ F. W. Peek, Jr., High Voltage Engineering, Journal Franklin Institute, Dec., 1913.
160
DIELECTRIC PHENOMENA
saturation is reached. Qo and a vary to a considerable extent in oil. The strength of oil, or the disruptive gradient, or the gradi- ent required to bring the ions up to collision velocity, seems fairly low. Oil should, therefore, have low strength in bulk, but high
TOO 600
8400
5800 •800
100
v
1
V
"V
^
SJ
■-.
h.
^
.i
«
-1
K)
1
1 1
1
1
4
BpacRiff em.
Fia. 145. — Showing increase of strength of oil at small spacings.
(Spheres, R » 3.33 cm.)
WO
04A
840
S8U
260
140 QooA
ssso
^aoo
H IDU
\
JJ 140
C lOA
\
^
o i«o
4AA
V
N^
100
QA
"^
AA
"^
^^
-.
00
40
OA
sso
A
L 1
I \
K <
i 1
5 (
J -i
' 8
; i
} 1
.0 1
1 1
2 18
Badlai*em.
Fia. 146. — Strength of oil between spheres. (Data from constant part of the curve.)
apparent strength when sub-divided or confined to make use of the large energy distance necessary to rupture.
Spark-over voltages and gradients are given for various spheres
CORONA AND SPARK-OVER IN INSULATIONS
161
at various spacings in Table LXIV. The characteristics of the curves between gradient and spacing are the same as those for air (see Fig. 42) as shown in Fig. 145. When the spacing is so small that it interferes with the energy distance the apparent strength of oil increases. At spacings above this the gradient is constant until the separation is so great that corona forms before spark-over.
Table LXVIII. — Spheres in Oil
Provenance
- Shelf
- Reference library
- Author
- F.W. Peek Jr.
- Rights
- Published in 1915, before 1929, and therefore in the public domain in the United States.
- Collected By
- StanBot reference library